Every facet of our daily life is being automated by faster microprocessors and microprocessor-based equipment which require steady continuous power. As market pressures force the deregulation of the electrical industry, utility companies have less and less control over the quality of power supplied to sensitive electronic equipment. In industry, the effects of unreliable power can be seen in the erroneous motion of computer-controlled milling machines, causing irreparable damage to expensive manufacturing equipment or finished products. Additionally, poor power quality can cause motor driven equipment to operate inefficiently and overheat, causing premature failure. In data processing and medical applications, the effects of unreliable power can be translated into incorrect data, lost memory, premature component failure, mixed and garbled data and inaccurate diagnostics. Power conditioning alleviates these problems.

 

Specifications

General Information
ManufacturerEaton Corporation
Brand NameEaton
Product LinePower-Sure
Product ModelT800F-10000
Product TypeLine Conditioner
Technical Information
Protection Type
  • Lightning
  • AC Surge
  • Harmonics
  • AC Noise
  • Plug/Connector TypeHardwired
    ReceptaclesHardwired
    Power Description
    Load Capacity10 kVA/10 kW
    Input Voltage
  • 208 V AC
  • 240 V AC
  • 480 V AC
  • Output Voltage120 to 240 V AC
    Frequency50 Hz
    Physical Characteristics
    Height28.5"
    Width23"
    Depth20"
    Weight (Approximate)507 lb
    Miscellaneous
    Additional Information
    • Line Regulation: +/- 2% Vout for +10% to -20% Vin at 100% Load
    • Load Regulation: +/-3% for 0% to 100% load
    • Immunity to Distortion: @40% THD Vin, 5% Max THD Vout
    • Ride-through Capability: 1 cycle
    • Voltage Recovery: 2 cycles to 95%, 3 cycles to 100%
    • K-Factor: K-30 Rated
    • Power Factor Correction: Input of 0.95 typical
    • Harmonic Attenuation: -23dB for load reflected harmonics
    • Galvanic Isolation: NEC 250-5d, 0.001 pf
    • Surge Protection: UL 1449 Rating 330v; ANSI/IEEE C62.41-Cat B3
    • Common Mode Noise Attenuation: 140 dB
    • Transverse Mode Noise Attenuation: 120 dB
    • Reliability: 200,000 hours (MTBF)
    • Audible Noise: 1 meter A scale, 52dB to 56dB
    • Efficiency: Approx. 92% at full load